Miniature circuit breaker 16 A 1P+N

Item number: CH-10-11

EAN: 3606480440120

Miniature circuit-breaker iC60N with one phase plus neutral circuit, 16 A, characteristic B

24,99 €

including 20% VAT. , plus shipping (Klein)

Shipping time: 7 days



The circuit to which the go-eCharger is connected has to be equipped with a miniature circuit breaker (characteristic B or C) of the following specification:

  • Connection 16 A or 32 A three-phase = 3- or 4-pole miniature circuit breaker for 16 A or 32 A
  • Connection 16 A or 32 A single-phase = 2-pole miniature circuit-breaker for 16 A or 32 A

The miniature circuit breaker offered here is suitable for the single-phase connection of the go-eCharger with a maximum of 16 A.

Main characteristics:

  • Series/product name: Acti 9 iC60N
  • Product or component type: Miniature circuit-breaker (MCB)
  • Poles description: 1P + N
  • Neutral position: left
  • Rated current: 16 A
  • Network type: AC / DC
  • trip unit technology: thermal-magnetic
  • characteristic: B
  • breaking capacity:
    • 10 kA Icu conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz
    • 20 kA Icu conforming to EN/IEC 60947-2 - 100...133 V AC 50/60 Hz
    • 6000 A Icn conforming to EN/IEC 60898-1 - 230 V AC 50/60 Hz
    • 36 kA Icu conforming to EN/IEC 60947-2 - 12...60 V AC 50/60 Hz
  • utilisation category: category A conforming to EN/IEC 60898-1
  • suitability for isolation: yes conforming to EN/IEC 60947-2 and EN/IEC 60898-1

Additional features:

  • Network frequency: 50/60 Hz
  • magnetic tripping limit: 4 x In +/- 20 %
  • [Ics] rated service breaking capacity:
    • 6000 A 100 % x Icu conforming to EN/IEC 60898-1 - 230 V AC 50/60 Hz
    • 27 kA 75 % x Icu conforming to EN/IEC 60947-2 - 12...60 V AC 50/60 Hz
    • 7.5 kA 75 % x Icu conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz
    • 15 kA 75 % x Icu conforming to EN/IEC 60947-2 - 100...133 V AC 50/60 Hz
  • limitation class: 3 conforming to EN/IEC 60898-1
  • [Ui] rated insulation voltage: 500 V AC 50/60 Hz conforming to EN/IEC 60947-2
  • [Uimp] rated impulse withstand voltage: 6 kV conforming to EN/IEC 60947-2
  • contact position indicator: available
  • Operating mode: toggle switch
  • local signalling: trip indicator
  • Mounting bracket: DIN rail
  • 9 mm pitch: 4
  • Dimensions (height x width x depth): approx. 91 x 36 x 78,5 mm
  • Colour: white
  • Mechanical durability: 20,000 cycles
  • Electrical durability: 10,000 cycles
  • Connections – terminals: biconnect, top or bottom rigid wire(s) 1...25 mm˛ max or biconnect, top or bottom flexible wire(s) 1...16 mm˛ max
  • Wire stripping length: 14 mm (top or bottom)
  • Tightening torque: 2 Nm (top or bottom)
  • earth-leakage protection: separate block

Assembly:

  • IP degree of protection:  IP20 conforming to EN/IEC 60529
  • Pollution degree: 3
  • Overvoltage category: IV
  • Relative humidity: 95 % at 55 °C
  • Ambient air temperature for operation: -35...70 °C
  • Ambient temperature during storage: -40...85 °C

Shipping weight: 0.54 Kg